APC Power-Saving Back-UPS Pro 1000VA (BR1000G)
The official replacement cartridge for the BR1000G is APCRBC123, a 24 V, 7 Ah lead-acid cartridge with a 2-year repair-or-replace warranty. Do not order the successor BR1000MS battery for this unit.
Official replacement cartridge
APCRBC123
| Official SKU | APCRBC123 |
|---|---|
| Voltage | 24 V |
| Capacity | 7 Ah |
| Type | Lead-acid (VRLA) |
| Cartridge quantity | 1 |
| Cartridge warranty | 2-year repair or replace |
| Assembly | 7 Ah, 24 Vdc replaceable cartridge for APC Back-UPS and Smart-UPS line-interactive units; Canadian official page also lists all required connectors, an installation guide, and reusable packaging |
Official APCRBC123 product page
UPS specifications (from the official datasheet or product page)
| Family / product name | APC Power-Saving Back-UPS Pro 1000VA (BR1000G) |
|---|---|
| VA rating | 1000 VA |
| Watt rating | 600 W |
| Topology | Line interactive |
| Waveform | Stepped approximation to a sine wave |
| Input voltage | 120 V |
| Form factor | Tower (not rack-mountable) |
| Outlets | 8 × NEMA 5-15R (4 battery + surge, 4 surge-only) |
| Transfer time | 8 ms typical, 12 ms maximum |
| Typical recharge time | 8 hours (typical) |
| Typical battery life | 3–5 years |
| Official RBC quantity | 1 |
| User-replaceable battery | Yes (official Back-UPS table: user-replaceable battery) |
| UPS warranty (as published) | 36 months (UPS), 12 months (battery supplied with the UPS) |
| Equipment protection policy | Lifetime: $150,000 |
Related models
- BX1350M, BX1000G, BX1300G: Schneider’s official USA/Canada table lists APCRBC123 for the BX1350M. The official Back-UPS XS/RS “G” install FAQ also assigns APCRBC123 to BX1000G, BX1000G-CA, BX1300G, and BX1300G-CA. Confirm the label on your unit.
- BR1000MS: Schneider lists BR1000MS as the official replacement for the discontinued BR1000G. The official USA/Canada table and the BR1000MS datasheet assign APCRBC160 to the BR1000MS, not APCRBC123. Open the BR1000MS guide for that cartridge.
- BR1500G: A close “G” family relative, but the official cartridge is APCRBC124 (24 V, 9 Ah), not APCRBC123.
How to replace the battery
Schneider publishes a battery-installation video for the Back-UPS XS/RS “G” family that includes the BR1000G and points to APCRBC123. Follow that official procedure and the instruction sheet in the cartridge box. This UPS is past its official end-of-service date.
Official installation video: https://www.se.com/us/en/faqs/FA158954/
- Confirm the rear or bottom label says BR1000G. The successor BR1000MS uses APCRBC160, and the BR1500G uses APCRBC124.
- Watch Schneider’s official Back-UPS XS/RS “G” battery installation video and read the APCRBC123 instruction sheet.
- If you are not sure the unit can be serviced live, shut it down and unplug it before opening the battery compartment.
- Install the complete APCRBC123 cartridge as a unit. Recycle the used pack (the official cartridge page notes support for APC-authorized recycling).
- Allow the official typical 8-hour recharge before judging runtime, then check that a replace-battery indicator has cleared.
These are orientation steps, not a substitute for the manufacturer’s instruction sheet. Lead-acid UPS batteries can present electrical and chemical hazards.
Warranty considerations
- A separately purchased APCRBC123 is advertised with a 2-year repair-or-replace warranty. The official Canadian APCRBC123 specifications list a 24-month contractual warranty, 24 V battery voltage, and 7.0 Ah capacity.
- The BR1000G datasheet lists 12 months of battery coverage on the pack that shipped with the UPS, 36 months on the UPS, and a lifetime $150,000 equipment protection policy.
- Using a non-APC battery will void APC’s Equipment Protection Policy, according to Schneider Electric FAQ FA328895.
- Standard service for the BR1000G ended on November 12, 2022. Official repair and spare-parts service may no longer be available even if genuine cartridges are still sold.
When to replace the whole UPS instead
- The BR1000G is past both its commercialization date (December 6, 2021) and its official end of standard service (November 12, 2022). Schneider lists the BR1000MS as the replacement model.
- If you replace the UPS with a BR1000MS, order APCRBC160 later — not APCRBC123.
- If a new genuine APCRBC123 does not restore normal operation after a full charge, the chassis may have failed. Official maintenance service is no longer listed as available.
- This unit outputs a stepped approximation to a sine wave. If connected equipment now needs a sine-wave UPS, replace the unit rather than the battery.
Where to buy (affiliate placeholders)
These are ordinary search links, not tracked affiliate tags. When a program is joined, replace the href and keep the data-affiliate attribute.
Search Amazon for APC APCRBC123 Affiliate placeholderSearch eBay for APC APCRBC123 Affiliate placeholder
FAQ
What battery does a BR1000G take?
The official BR1000G datasheet, Schneider’s USA/Canada Back-UPS table, and the Back-UPS XS/RS “G” installation FAQ all list APCRBC123. The official APCRBC123 page describes it as a 24 V, 7 Ah lead-acid cartridge with a 2-year repair-or-replace warranty.
Can I use APCRBC124 because I have a Back-UPS Pro “G” unit?
No. Official documentation assigns APCRBC124 to the BR1500G and BX1500M, and APCRBC123 to the BR1000G. They are both 24 V cartridges, but the official capacities differ (7 Ah vs 9 Ah).
My unit says BR1000MS. Is that the same cartridge?
No. Schneider lists the BR1000MS as the successor to the BR1000G, and the official USA/Canada table assigns APCRBC160 to the BR1000MS.
Sources
- APC BR1000G product datasheet (replacement battery APCRBC123; 1000 VA / 600 W; discontinued December 6, 2021; end of service November 12, 2022)
- APC BR1000G product page (discontinued December 6, 2021; end of service November 12, 2022; replaced by BR1000MS)
- Official USA/Canada Back-UPS replacement battery table (BR1000G = APCRBC123; BR1000MS = APCRBC160)
- APCRBC123 official U.S. product page (24 V, 7 Ah, 2-year warranty)
- APCRBC123 official Canadian specifications (24 V, 7.0 Ah, 24-month warranty)
- Back-UPS XS/RS “G” battery installation video (BR1000G → APCRBC123)
- Why use only a genuine APC RBC